Blog · Warehouse heat loss

Dock doors and dock seals: how much money escapes?

A worn dock seal looks dramatic on a thermal image. But what does it really cost? An example warehouse, in forints, with ranges, and an honest look at where the bigger money is.

The short answer

In the example warehouse, one worn dock seal is estimated to cost HUF 18,000 in heating per season (range: 15,000–26,000). That is less than the bright streak on the thermal image suggests. The dock-related items together – four failed seals, four leveller pits and the perimeters of the closed doors – make up 6.5% of the example's estimated loss; roof gaps and wet roof insulation make up 75%.

That does not mean docks do not matter: cold air streaming in beside a trailer can cause comfort problems, condensation and ice around the leveller, none of which the model puts a price on. But if the aim is to cut the gas bill, it pays to do the repairs in the order the numbers give. A thermal survey produces exactly that order.

Where does a dock leak?

Around a loading door there are four typical places where cold air gets in and warm air escapes. The dock shelter (side pads and head curtain) only counts while a trailer is docked; when there is none, the door's own perimeter seals do the work. The leveller pit under the dock leveller is open in both cases.

1 2 3 4
  1. Side pads: compressed or torn dock shelter between trailer and opening
  2. Head curtain: missing or curled-up section
  3. Leveller pit: side gaps around the dock leveller
  4. Closed-door perimeter: worn seals when no trailer is docked
Schematic, not to scale. Orange sections mark the gaps, arrows show cold air coming in.

How much money escapes? The example hall

The example is a 60 × 40 m (2,400 m²) warehouse: sandwich-panel walls and roof, 16 °C, gas radiant-tube heating, four dock doors and two sectional doors, near Nyíregyháza. We took the “extensive” defect level: all four dock seals failed, the leveller-pit side gaps open, and the roof and panel joints poor as well. The calculation uses the October 2026 net gas price: 40.4 HUF/kWh central (range 32.1–56.9 HUF/kWh) and a heating efficiency of 0.80.

Estimated heating cost by item, HUF/season (central) HUF/season Estimate Example
  • 1 dock seal (failed, 7.6 m × 26 mm gap) HUF 18,000
  • 4 leveller-pit side gaps HUF 66,000
  • 4 dock-door perimeters when closed HUF 38,000
  • 1 sectional door with worn seals HUF 42,000
  • Roof-ridge gap (60 m × 3 mm) HUF 690,000
  • 8 skylight perimeter gaps HUF 610,000
  • Wet roof insulation (140 m²) HUF 740,000
  • Wall-panel joints (90 m × 2 mm) HUF 360,000
Estimated cost and repair – example warehouse with extensive defects
Item Est. loss, HUF/seasonRepair (indicative), HUFSimple paybackPrio.
1 dock seal (failed, 7.6 m × 26 mm gap) HUF 18,000 (15,000–26,000) HUF 300,000 (150,000–600,000) 16 yr C
4 leveller-pit side gaps HUF 66,000 (53,000–93,000) HUF 600,000 (320,000–1,200,000) 9.1 yr C
4 dock-door perimeters when closed HUF 38,000 (30,000–54,000) HUF 360,000 (160,000–720,000) 9.4 yr C
1 sectional door with worn seals HUF 42,000 (33,000–59,000) HUF 90,000 (40,000–180,000) 2.1 yr B
Roof-ridge gap (60 m × 3 mm) HUF 690,000 (550,000–970,000) HUF 270,000 (150,000–480,000) 0.4 yr A
8 skylight perimeter gaps HUF 610,000 (480,000–860,000) HUF 960,000 (480,000–2,000,000) 1.6 yr A
Wet roof insulation (140 m²) HUF 740,000 (590,000–1,000,000) HUF 3,100,000 (1,700,000–5,600,000) 4.1 yr B
Wall-panel joints (90 m × 2 mm) HUF 360,000 (290,000–510,000) HUF 410,000 (230,000–720,000) 1.1 yr A

Estimate – not a guarantee. Figures are model-based and actual values may differ.

The total estimated loss of the example is HUF 2,700,000 per season (range 2,200,000–3,900,000), which is 26.6% of the heating bill. Figures are rounded to two significant digits: the uncertainty of an individual estimate is typically ±30–50%.

The loss per dock depends on utilisation. The model assumes a dock gap leaks during about 25% of heated hours, when a trailer is docked with the door open; on a site with continuous loading it can be higher, and with occasional service lower.

Why the docks do not lose the most

  • Gap length. A dock-shelter side gap is an opening of a few tenths of a square metre. The roof-ridge gap is 60 m long and the eight skylights have 80 m of perimeter in total: long, continuous gaps, all season.
  • Building height. The calculation treats the hall as a two-level leakage network: what enters low must leave high. According to the model, most of the hall's air exchange is driven by the long roof gaps.
  • Wet roof insulation. Only 140 m² (about 6% of the roof) is the largest single item, because the conductivity of wet insulation is many times that of an intact panel.

What the camera shows at a dock

From outside at night, warm air escaping through a gap appears as a bright streak along the side pads, under the head curtain and around the leveller pit. From inside, incoming cold air draws a cold band on the floor and beside the ramp. The thermal image gives the location and approximate width of the leak; it does not read the watts lost, which we estimate from dimensions and a model.

A single image shows a single moment. How many hours a year a dock stands open is operating data: so we ask for an estimate of utilisation and record it as an assumption in the report. Timing matters as well; the conditions for an exterior survey are covered in a separate article.

Does the repair pay back?

The simple payback in the table follows from the indicative, quote-based repair cost and the estimated seasonal saving; the repair prices are assumptions. Three takeaways:

  • A dock-shelter repair (HUF 300,000 per dock, range 150,000–600,000) rarely pays back from heating savings alone: about 16 years in the example. It is more often justified by comfort, condensation or wear.
  • A sectional-door seal set (HUF 90,000) is cheap and would pay back in about 2.1 years in the example.
  • The fastest items are on the roof: sealing the ridge gap (HUF 270,000) would pay back in about 4.7 months, and resealing the wall-panel joints (HUF 410,000) in about 14 months.

Savings only materialise if the repair is carried out and works. The survey itself saves no energy; the ranking helps the money go where it returns most. You can try your own numbers in the payback calculator; the details of the examples are in the worked examples.

What you can do now

  • Inspect the dock shelters: compressed or cracked side pads, a curled-up or missing head curtain.
  • Check the bottom and side seals of sectional doors: is light visible around the door, can you feel a draught?
  • Make sure a dock without a trailer has its door closed.
  • Look at the leveller-pit side gaps; a brush or rubber-strip seal is a cheap measure.
  • The ridge, skylights and panel joints are hard to judge from the ground: these are worth a night-time survey.

A quote tailored to warehouse and logistics sites is on the warehouse and logistics page; the details of hall surveys are on the service page.